Gas Fire Extinguishing Controller/Fire Alarm Panel
Features:
Control and indicating equipment
★One detection loop with 64 maximum addressable points.
★Control function for 4 loops addressable passive normal open connectors.
★128*64 LCD for displaying in Chinese and English.
★Convertible between Chinese and English , comform to internationalization.
★Print out in Chinese.
★Black-box function, data storage up to 1000 fire alarm records, 500gas extinguishing records and 500 pieces of relevant information.
★Short circuit protection in the loop an power supply.
★CAN Bus communication interface, work with LD6900 series communication module, as zone CIE to network with other equipment.
★Addressing of field devices randomly.
Gas-extinguishing control and indicating equipment
★Multi-line output controlled directly on-scene equipments.
★Delay start(the delay time can be set randomly between 0 and 30 seconds)
★Auto start.
★On-scene emergence start/stop.
★Manual start.
★To stop the start function by manual in the delay start.
★Convert between manual and auto.
★Line fault detection function.
★One group passive normal open output control.
★Digital tube to display the count down in the process of delay time.
Main technology specifications:
Content |
Technical Data |
Power supply voltage |
AC 220V(187V-242V)50Hz |
Unload power |
≤ 4W |
Operating temperature |
0ºC~45ºC |
Relative humidity |
≤ 95%RH(40±2ºC) |
Mounting method |
Wall-mounted |
Battery |
2*12V/7Ah |
Max. External dimension |
428(W)mm×145(D)MM×560(H)mm |
Weight |
11.10kg ± 0.2kg |
Control and indicating equipment |
Output level to the loop |
DC14V~24V |
Number of loop |
1 |
Max. Number of addressable codes |
64 |
Max. Output current to the loop |
200mA |
Max. Protection current for short-circuit |
400mA |
Number of output connector |
4 loops addressable passive normally open connectors |
Gas-extinguishing control and indicating equipment |
Quantity of the controlling protective area |
1 |
Output voltage |
DC24V |
Max. Output current |
1A |