Gas Fire Detection System and Alarm System

Product Details
Customization: Available
Type: Industry Alarm
Signal Transmission: Wired Alarm
Gold Member Since 2015

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Management System Certification
ISO 9001
Terms of Payment
LC, T/T
  • Gas Fire Detection System and Alarm System
  • Gas Fire Detection System and Alarm System
Find Similar Products

Basic Info.

Model NO.
LD5507
Certification
CE, ISO, CCC, Cccf, Lpcb, CCS, CNAS, ILAC-MRA
Application
Fire Fighting
Transmission Mode
Cable
Material
Stainless Steel
Transport Package
Standard Export Packing
Specification
GB
Trademark
GQ
Origin
China
Production Capacity
1000000 PCS/Year

Product Description

Fire alarm Unit/Gas-extinguishing Control and Indicating Equipment

Gas Fire Detection System and Alarm System

Features:
Control and indicating equipment
★One detection loop with 60 maximum addressable points
★Function of common fire alarm and common passive normal open connector output.
★128*64 LCD for displaying in Chinese.
★Data storage up to 1000 fire alarm records, 1000 gas-extinguishing records and 1000 pieces of other information.
★CAN bus communication interface, as zone CIE to network with other equipment.
★Short circuit protection in the loop and power supply.
★Print out in Chinese.
 
 Gas-extinguishing control and indicating equipment
★One loop gas-extinguishing multiline output controlled directly on-scene equipments.
★Delay start(the delay time can be set randomly between 0~30 seconds).
★Auto start.
★On-scene emergence start/stop, up to connect 5 analogue addressable on-scene emergency start/stop press button(LD1200EN).
★Manual start.
★To stop the start function by manual in the delay start.
★Convert between manual and auto.
★Line fault detection function.
★Gas sprinkling passive normal open output.
 
Main technology specifications:
Content Technical Data
Power supply voltage AC 220V(187V-242V)50Hz
Unload power ≤ 10W
Operating temperature 0ºC~45ºC
Relative humidity ≤ 95%RH(40±2ºC)
Mounting method Wall-mounted
Battery 2*12V/7Ah
Max. External dimension 484(W)mm×122(D)MM×420(H)mm
Weight 8.20kg ± 0.1kg
 Control and indicating equipment
Output level to the loop DC14V~24V
Number of loop 1
Max. Number of addressable codes 60
Max. Output current to the loop 200mA
Audio and video output current 0.1A
Number of output connector Common fire alarm and common passive normally open connector
Gas-extinguishing control and indicating equipment
Quantity of the controlling protective area 1
Bottle start output level DC24V
Max. Output current of bottle 2A
Quantity of on-scene emergency press button 5
24V output current 0.3A
Capacity of current power-off normally open point 1A
Current of gas release light 0.2A
Audio and video alarm Analogue addressable

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.