Fire alarm Unit/Gas-extinguishing Control and Indicating Equipment
Features:
Control and indicating equipment
★One detection loop with 60 maximum addressable points
★Function of common fire alarm and common passive normal open connector output.
★128*64 LCD for displaying in Chinese.
★Data storage up to 1000 fire alarm records, 1000 gas-extinguishing records and 1000 pieces of other information.
★CAN bus communication interface, as zone CIE to network with other equipment.
★Short circuit protection in the loop and power supply.
★Print out in Chinese.
Gas-extinguishing control and indicating equipment
★One loop gas-extinguishing multiline output controlled directly on-scene equipments.
★Delay start(the delay time can be set randomly between 0~30 seconds).
★Auto start.
★On-scene emergence start/stop, up to connect 5 analogue addressable on-scene emergency start/stop press button(LD1200EN).
★Manual start.
★To stop the start function by manual in the delay start.
★Convert between manual and auto.
★Line fault detection function.
★Gas sprinkling passive normal open output.
Main technology specifications:
Content |
Technical Data |
Power supply voltage |
AC 220V(187V-242V)50Hz |
Unload power |
≤ 10W |
Operating temperature |
0ºC~45ºC |
Relative humidity |
≤ 95%RH(40±2ºC) |
Mounting method |
Wall-mounted |
Battery |
2*12V/7Ah |
Max. External dimension |
484(W)mm×122(D)MM×420(H)mm |
Weight |
8.20kg ± 0.1kg |
Control and indicating equipment |
Output level to the loop |
DC14V~24V |
Number of loop |
1 |
Max. Number of addressable codes |
60 |
Max. Output current to the loop |
200mA |
Audio and video output current |
0.1A |
Number of output connector |
Common fire alarm and common passive normally open connector |
Gas-extinguishing control and indicating equipment |
Quantity of the controlling protective area |
1 |
Bottle start output level |
DC24V |
Max. Output current of bottle |
2A |
Quantity of on-scene emergency press button |
5 |
24V output current |
0.3A |
Capacity of current power-off normally open point |
1A |
Current of gas release light |
0.2A |
Audio and video alarm |
Analogue addressable |