• Addressable Fire Alarm System Panel/ Controller/Linkage Type
  • Addressable Fire Alarm System Panel/ Controller/Linkage Type
  • Addressable Fire Alarm System Panel/ Controller/Linkage Type
  • Addressable Fire Alarm System Panel/ Controller/Linkage Type
  • Addressable Fire Alarm System Panel/ Controller/Linkage Type

Addressable Fire Alarm System Panel/ Controller/Linkage Type

Type: Industry Alarm
Signal Transmission: Wired Alarm
Certification: CE, ISO, CCC, Cccf,Lpcb, CCS, CNAS, ILAC-MRA
Application: Fire Fighting
Transmission Mode: Cable
Material: Stainless Steel
Customization:
Gold Member Since 2015

Suppliers with verified business licenses

Rating: 5.0/5
Trading Company

Basic Info.

Model NO.
LD128EN(M)
Transport Package
Standard Export Packing
Specification
GB
Trademark
GQ
Origin
China
Production Capacity
1000000 PCS/Year

Product Description

Fire alarm controller(Linkage type)
Addressable Fire Alarm System Panel/ Controller/Linkage Type
Features:
★Capacity of the panel:
Number of loop: 2
Max.addressable points: 512
Manual control panel: 1(8 loop output, including 1 loop special output of sound and light alarm)
★One pair of passive connector for common alarm, one for common fault connector output
★Print information function for Chinese and/or English.
★On-scene data set by CIE and/or SD card.
★CANBus interface, zone CIE to connector other equipment by LD6900 communication module.
(CANBus, RS232, RS485, Ethernet, Telephone line, GPRS).
★128*64 LCD displays, Indicator lights indicate critical status, easy to operate..
★Convertible between Chinese and English , comform to internationalization.
★Black-box function, data storage up to 1000 fire alarm records, 1000 gas extinguishing records and 1000 pieces of relevant information.
★External equipment can be controlled using either the BUS or multi-line panel.
★Short circuit protection in the loop an power supply.
★Alarm supervisory function.
 
Main technology specifications:
Content Technical Data
Power supply voltage AC 220V(187V-242V)50Hz
Output voltage to the loop DC14V~24V
Output to the panel DC24V/4A
Number of loop 2
Number of output connector 8 loop(including one loop sound and light) connected output.
Max. Number of addressable codes 512(single loop total number of address: 258)
Max. Output current to the loop 200mA
Max. Protection current for short-circuit 400mA
Unload power ≤ 5W
Operating temperature 0ºC~45ºC
Relative humidity ≤ 95%RH(40±2ºC)
Mounting method Wall-mounted
Battery 2*12V/14Ah
Max. External dimension 440(W)mm×160(D)MM×580(H)mm
Weight 11.20kg ± 0.1kg(Excluding battery)

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Gold Member Since 2015

Suppliers with verified business licenses

Rating: 5.0/5
Trading Company
Management System Certification
ISO 9001
Terms of Payment
LC, T/T